[Federal Register Volume 69, Number 115 (Wednesday, June 16, 2004)]
[Rules and Regulations]
[Pages 33536-33551]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 04-13522]
=======================================================================
-----------------------------------------------------------------------
NUCLEAR REGULATORY COMMISSION
10 CFR Part 50
RIN 3150-AG48
Voluntary Fire Protection Requirements for Light Water Reactors;
Adoption of NFPA 805 as a Risk-Informed, Performance-Based Alternative
AGENCY: Nuclear Regulatory Commission.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The Nuclear Regulatory Commission (NRC) is amending its fire
protection requirements for nuclear power reactor licensees to permit
existing reactor licensees to voluntarily adopt fire protection
requirements contained in the National Fire Protection Association
(NFPA) Standard 805, ``Performance-Based Standard for Fire Protection
for Light Water Reactor Electric Generating Plants, 2001 Edition''
(NFPA 805). These fire protection requirements are an alternative to
the existing deterministic, prescriptive fire protection requirements.
DATES: Effective: July 16, 2004. The incorporation by reference of the
publication listed in the regulation is approved by the Director of the
Federal Register as of July 16, 2004.
ADDRESSES: The final rule and related documents may be examined and
copied for a fee at the NRC Public Document Room (PDR), One White Flint
North, Room O1-F15, 11555 Rockville Pike, Rockville, Maryland (NFPA
standards are copyrighted). Copies of NFPA 805 may be purchased from
the NFPA Customer Service Department, 1 Batterymarch Park, P.O. Box
9101, Quincy, MA 02269-9101 and in PDF format through the NFPA Online
Catalog (www.nfpa.org) or by calling 1-800-344-3555 or (617) 770-3000.
FOR FURTHER INFORMATION CONTACT: Joseph L. Birmingham, Office of
Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission,
Washington, DC 20555-0001; telephone (301) 415-2829; e-mail
[email protected].
SUPPLEMENTARY INFORMATION:
I. Background
II. Discussion
III. Comment Resolution on Proposed Rule
IV. Section-by-Section Analysis
V. Availability of Documents
VI. Voluntary Consensus Standards
VII. Finding of No Significant Environmental Impact: Availability
VIII.Paperwork Reduction Act Statement
IX. Regulatory Analysis
[[Page 33537]]
X. Regulatory Flexibility Certification
XI. Backfit Analysis
XII. Small Business Regulatory Enforcement Fairness Act
I. Background
In 1971, the Atomic Energy Commission promulgated General Design
Criterion (GDC) 3, ``Fire protection,'' in Appendix A to 10 CFR part
50. Subsequently, the NRC developed specific guidance for implementing
GDC 3 in Branch Technical Position (BTP) Auxiliary and Power Conversion
Systems Branch (APCSB) 9.5-1, ``Guidelines for Fire Protection for
Nuclear Power Plants,'' dated May 1, 1976, and Appendix A to BTP APCSB
9.5-1, ``Guidelines for Fire Protection for Nuclear Power Plants
Docketed Prior to July 1, 1976,'' dated August 23, 1976. In the late
1970s, the NRC worked with licensees to establish configurations to
meet this guidance, reaching closure on most issues. However, to
resolve the remaining contested issues, the NRC published the final
fire protection rule (10 CFR 50.48, ``Fire protection'') and Appendix R
to 10 CFR part 50 dated November 19, 1980 (45 FR 76602).
Section 50.48(a)(1) requires each operating nuclear power plant to
have a fire protection plan that satisfies Criterion 3 (GDC 3) of
Appendix A to 10 CFR 50 and states that the fire protection plan must
describe the overall fire protection program; identify the positions
responsible for the program and the authority delegated to those
positions; outline the plans for fire protection, fire detection and
suppression capability, and limitation of fire damage. Section
50.48(a)(2) states that the fire protection plan must describe the
specific features necessary to implement the program described in
paragraph (a)(1) including administrative controls and personnel
requirements; automatic and manual fire detection and suppression
systems; and the means to limit fire damage to structures, systems, and
components (SSCs) to ensure the capability to safely shut down the
plant. Section 50.48(a)(3) requires that the licensee retain the fire
protection plan and each change to the plan as a record until the
Commission terminates the license.
GDC 3, referenced in 10 CFR 50.48(a)(1), provides broad performance
objectives for an acceptable fire protection program. GDC 3 specifies,
in part, that SSCs important to safety be designed and located to
minimize, consistent with other safety requirements, the probability
and effects of fires and explosions; noncombustible and heat resistant
materials be used wherever practical; fire detection and fighting
systems of appropriate capacity and capability be provided and designed
to minimize the adverse effects of fires on SSCs important to safety;
and fire fighting systems be designed to assure their rupture or
inadvertent operation does not significantly impair the safety
capability of the SSCs.
Section 50.48(b) references Appendix R to 10 CFR 50 and states that
Appendix R establishes fire protection features required to satisfy GDC
3 with respect to certain generic issues for nuclear power plants
licensed to operate before January 1, 1979. As stated in 10 CFR
50.48(b)(1), with the exception of Sections III.G, III.J, and III.O of
Appendix R, nuclear power plants that were licensed to operate before
January 1, 1979, are exempt from the requirements of Appendix R. These
plants are exempt to the extent that:
Features proposed or implemented by the licensee have been accepted
by the NRC staff as satisfying the provisions of Appendix A to BTP
APCSB 9.5-1 that are reflected in NRC fire protection safety evaluation
reports (SERs) issued before the 10 CFR 50.48 effective date of
February 19, 1981; or,
Features that were accepted by the NRC staff in comprehensive SERs
before Appendix A to BTP APCSB 9.5-1 was published in August 1976.
Otherwise, these nuclear power plants must meet 10 CFR 50, Appendix R,
as well as any requirements contained in plant specific fire protection
license conditions and/or technical specifications. These nuclear power
plants must also comply with 10 CFR 50.48(a).
Nuclear power plants that were licensed to operate after January 1,
1979, must comply with 10 CFR 50.48(a) as well as any plant-specific
fire protection license conditions and/or technical specifications.
Their fire protection license conditions typically reference SERs
generated by the NRC as the product of initial licensing reviews
against either Appendix A to BTP APCSB 9.5-1 and the criteria of
certain sections of 10 CFR 50, Appendix R, or Section 9.5.1 of NUREG-
0800, the NRC Standard Review Plan (SRP) which includes similar
criteria specified in 10 CFR 50, Appendix R. These fire protection
requirements are considered to be deterministic.
The NRC has issued approximately 900 exemptions from the technical
requirements specified in Appendix R. These exemptions were granted to
licensees that submitted a technical evaluation demonstrating that an
alternative fire protection approach satisfied the underlying safety
purpose of Appendix R. During the initial implementation period for
``Pre-1979 Appendix R plants,'' the NRC granted exemptions under the
provisions of 10 CFR 50.48(c)(6), which has since been deleted. For
exemptions requested by ``Pre-1979 plants'' after the licensee's
initial Appendix R implementation period, the NRC conducted its reviews
in accordance with the provisions specified in 10 CFR 50.12, ``Specific
exemptions.'' ``Post-1979 plants'' have also requested and, when
acceptable to the NRC, received approval to deviate from their
licensing requirements. The processing of exemption and deviation
requests has placed a significant burden on the resources of the NRC
and the nuclear industry.
Industry representatives and some members of the public have
described the current deterministic fire protection requirements as
``prescriptive'' and an ``unnecessary regulatory burden.'' Beginning in
the late 1990s, the Commission provided the NRC staff with guidance for
identifying and assessing performance-based approaches to regulation
(see SECY-00-0191, ``High-Level Guidelines for Performance-Based
Activities,'' dated September 1, 2000, and Staff Requirements
Memorandum (SRM), dated March 1, 1999, entitled, ``SECY-98-0144: White
Paper on Risk-Informed and Performance-Based Regulation.'' This
guidance augmented the risk-related guidance in the NRC's Probabilistic
Risk Assessment (PRA) Policy Statement (60 FR 42622, August 16, 1995)
and Regulatory Guide (RG) 1.174, ``An Approach for Using Probabilistic
Risk Assessment in Risk-Informed Decisions on Plant-Specific Changes to
the Licensing Basis,'' dated July 1998.
In SECY-98-0058, ``Development of a Risk-Informed, Performance-
Based Regulation for Fire Protection at Nuclear Power Plants,'' dated
March 26, 1998, the NRC staff proposed to the Commission that the staff
work with the NFPA and the industry to develop a performance-based,
risk-informed consensus standard for fire protection for nuclear power
plants and, if the standard was acceptable, the staff would endorse the
standard in a rulemaking. In an SRM dated June 30, 1998, the Commission
approved the staff's proposal and the staff began cooperative
participation in the development of NFPA 805.
As a result of its interaction with NFPA, the NRC staff determined
that the likelihood of an acceptable standard was sufficiently high
that rulemaking to endorse NFPA 805 should be approved. In SECY-00-
0009, dated January 13, 2000, titled ``Rulemaking Plan, Reactor
[[Page 33538]]
Fire Protection Risk-Informed, Performance-Based Rulemaking,'' the
staff requested Commission approval to proceed with rulemaking to
permit reactor licensees to adopt NFPA 805 as a voluntary alternative
to existing fire protection requirements. In an SRM dated February 24,
2000, the Commission directed the staff to proceed with this
rulemaking.
The NFPA Standards Council issued NFPA 805, 2001 Edition, January
13, 2001, with an effective date of February 9, 2001. It was approved
as an American National Standard on February 9, 2001. The standard
specifies the minimum fire protection requirements for existing light
water nuclear power plants during all modes (``phases'' in NFPA 805) of
plant operation, including, shutdown, degraded conditions, and
decommissioning.
In a memorandum dated October 9, 2001, the NRC staff informed the
Commission that it planned to submit to the Commission by July 2002 a
proposed rule that would revise 10 CFR 50.48 and a final rule 12 months
after the proposed rule was published for public comment. Additionally,
the staff informed the Commission that it was working with the Nuclear
Energy Institute (NEI) to develop implementing guidance.
On December 20, 2001 (66 FR 65661), the NRC published draft rule
language proposing to endorse NFPA 805 in the Federal Register. The NRC
also posted this draft language on the NRC's interactive Rulemaking
Forum Web site at http://ruleforum.llnl.gov. The NRC requested public
comment on the draft rule language.
In response to this preliminary request for public comment, the NRC
received five sets of comments from industry, consultants, licensees,
industry organizations, and NRC staff. Based on those comments and on
reviews by NRC Program Offices and Committees, the NRC revised the
draft rule language. In SECY-02-0132, dated July 15, 2002, the staff
requested the Commission's approval to publish the proposed rule in the
Federal Register and on October 3, 2002, the Commission approved the
publication of the proposed rule in the Federal Register for public
comment. The proposed rule was published in the Federal Register for a
75-day public comment period (67 FR 66578; November, 1, 2002).
II. Discussion
In this rule, the NRC is allowing licensees to adopt NFPA 805 as a
performance-based alternative to complying with paragraph (b) of Sec.
50.48 for plants licensed to operate before January 1, 1979; or the
fire protection license conditions for plants licensed to operate after
January 1, 1979. Paragraph (b) of Sec. 50.48 refers to fire protection
features that 10 CFR 50, Appendix R requires to satisfy GDC 3.
Paragraph (b) discusses the extent to which those features are
regulatory requirements for certain licensees, and specifically to
plants licensed before January 1, 1979. Requirements for plants
licensed after that date are specified in plant fire protection license
conditions. The NRC considers that NFPA 805 specifies fire protection
requirements or provides an acceptable methodology and performance
criteria for licensees to identify fire protection requirements that
are an acceptable alternative to the Appendix R fire protection
features. A description of NFPA 805 and the NFPA 805 methodology
follows.
NFPA 805 is a performance-based standard for fire protection
prepared by the NFPA Technical Committee on Fire Protection for Nuclear
Facilities. Issued by the Standards Council on January 13, 2001, it was
approved as an American National Standard on February 9, 2001. NFPA 805
describes a methodology for establishing fundamental fire protection
program design requirements and elements, determining required fire
protection systems and features, applying performance-based
requirements, and administering fire protection for existing light
water reactors during operation, decommissioning, and permanent
shutdown. It provides for the establishment of a minimum set of fire
protection requirements but allows performance-based or deterministic
approaches to be used to meet performance criteria.
Under NFPA 805, a licensee adopts the performance goals,
objectives, and criteria itemized in Chapter 1 of NFPA 805 and then
meets those goals, objectives, and criteria through the implementation
of performance-based or deterministic approaches. Those goals,
objectives, and criteria contain provisions for nuclear safety,
radioactive release, life safety, and business interruption. Relative
to its mission to protect the public health and safety, the NRC is
concerned with the nuclear safety and radioactive release goals,
objectives, and criteria, and the protection of essential personnel
aspect of the life safety goals, objectives, and criteria. Therefore,
the NRC is not endorsing the Plant Damage/Business Interruption and
Life Safety Goals of NFPA 805.
After a licensee adopts the performance goals, objectives, and
criteria itemized in Chapter 1, it establishes plant fire protection
requirements using the methodology in Chapter 2 of NFPA 805. The
initial step in this methodology is to establish the minimum fire
protection program elements and design criteria contained in Chapter 3
of NFPA 805. NFPA 805 does not permit the Chapter 3 elements and design
criteria to be subject to the performance-based approaches allowed
elsewhere within NFPA 805. However, to provide regulatory flexibility,
the final rule provides for licensees to request a license amendment to
apply NFPA 805 performance-based approaches to the Chapter 3 fire
protection program elements and minimum design criteria.
After establishing the fundamental fire protection program elements
and minimum design requirements of Chapter 3, the licensee performs a
plant-wide analysis to identify fire areas and fire hazards required to
meet the performance criteria and the SSCs in each fire area to which
the performance criteria apply. The licensee may apply either a
performance-based or a deterministic approach to meet the performance
criteria. For a deterministic approach, the performance criteria are
deemed to be satisfied when the plants existing fire protection
requirements are met. For a performance-based approach, the licensee
must perform engineering analyses to demonstrate that the performance-
based requirements are met. These engineering analyses may include
engineering evaluations, probabilistic safety assessments, and fire
modeling calculations.
If the approach chosen to meet the performance criteria results in
a change to the approved design basis, the licensee must evaluate any
resulting changes in risk and determine whether the changes in risk are
acceptable to the AHJ (Authority Having Jurisdiction, i.e., NRC). NRC
guidance on the acceptability of changes in risk is in RG 1.174 and is
referenced by NFPA 805. The licensee must also evaluate the change to
determine whether defense-in-depth and safety margins are maintained.
The licensee implements a monitoring program to monitor plant
performance as it applies to fire risk and must adjust the fire
protection program as necessary as levels of risk change. For the
resulting fire protection program, the licensee documents the results
of the analyses, ensures the quality of the analyses, and maintains
configuration control of the resulting plant design and operation.
Section 2.7 of NFPA 805 provides requirements for program
documentation, configuration control, and quality.
[[Page 33539]]
NFPA 805 does not supersede the requirements of GDC 3, 10 CFR
50.48(a), or 10 CFR 50.48(f). Those regulatory requirements continue to
apply to licensees that adopt NFPA 805. However, under NFPA 805, the
means by which GDC 3 or 10 CFR 50.48(a) requirements may be met is
different than under 10 CFR 50.48(b). Specifically, whereas GDC 3
refers to SSCs important to safety, NFPA 805 identifies fire protection
systems and features required to meet the Chapter 1 performance
criteria through the methodology in Chapter 4 of NFPA 805. Also, under
NFPA 805, the 10 CFR 50.48(a)(2)(iii) requirement to limit fire damage
to SSCs important to safety so that the capability to safely shut down
the plant is ensured is satisfied by meeting the performance criteria
in Section 1.5.1 of NFPA 805. The Section 1.5.1 criteria include
provisions for ensuring that reactivity control, inventory and pressure
control, decay heat removal, vital auxiliaries, and process monitoring
are achieved and maintained.
This methodology specifies a process to identify the fire
protection systems and features required to achieve the nuclear safety
performance criteria in Section 1.5 of NFPA 805. Once a determination
has been made that a fire protection system or feature is required to
achieve the performance criteria of Section 1.5, its design and
qualification must meet any applicable requirements of NFPA 805,
Chapter 3. Having identified the required fire protection systems and
features, the licensee selects either a deterministic or performance-
based approach to demonstrate that the performance criteria are
satisfied. This process satisfies the GDC 3 requirement to design and
locate SSCs important to safety to minimize the probability and effects
of fires and explosions.
The methodology in NFPA 805 for performance-based approaches is to
a large degree consistent with the principles for performance-based
regulation contained in the ``White Paper on Risk-Informed,
Performance-Based Regulation,'' attached to the SRM for SECY-98-0144.
The NFPA 805 methodology incorporates the following attributes: (1)
Measurable or calculable parameters exist to monitor the system,
including facility performance; (2) objective criteria to assess
performance are established based on risk insights, deterministic
analyses, and/or performance history; (3) plant operators have the
flexibility to determine how to meet established performance criteria
in ways that will encourage and reward improved outcomes; and (4) a
framework exists in which the failure to meet a performance criterion,
while undesirable, will not in and of itself constitute or result in an
immediate safety concern.
Technical Acceptability of NFPA 805 as an Alternative to 10 CFR
50.48(b)
With respect to the certain required fire protection features
required to satisfy GDC 3, 10 CFR 50.48(b) references Appendix R,
whereas 10 CFR 50.48(c) references NFPA 805. The NRC evaluated whether
the technical approaches, methodologies, and engineering analyses
specified in NFPA 805 provide criteria to establish fire protection
features sufficient to satisfy GDC 3. The acceptability of NFPA 805
with exceptions and supplementation versus Appendix R is discussed
below.
Appendix R, Section I, states that Appendix R sets forth the fire
protection features required to satisfy GDC 3 with respect to certain
generic issues. Section I also discusses the need to limit fire damage
to systems required to achieve and maintain safe shutdown conditions
and that protection be provided so that a fire within only one such
system will not damage the redundant system.
Appendix R, Section II, provides the general requirements for a
fire protection program, discusses defense-in-depth, defines the fire
hazards analysis required to be performed, describes fire prevention
features, and requires alternate or dedicated shutdown capability for
areas where the fire protection features cannot ensure safe shutdown
capability in the event of a fire in that area.
Appendix R, Section III, provides specific requirements for certain
fire protection features. The fire protection features in Section III
are: A. Water supplies for fire suppression systems, B. Sectional
isolation valves, C. Hydrant isolation valves, D. Manual fire
suppression, E. Hydrostatic hose tests, F. Automatic fire detection, G.
Fire protection of safe shutdown capability, H. Fire brigade, I. Fire
brigade training, J. Emergency lighting, K. Administrative controls, L.
Alternative and dedicated shutdown capability, M. Fire barrier cable
penetration seal qualification, N. Fire doors, and O. Oil collection
system for reactor coolant pump.
NFPA 805 establishes performance goals, performance objectives, and
performance criteria that require a licensee to provide reasonable
assurance that a fire will not prevent the plant from achieving and
maintaining the fuel in a safe and stable condition, the plant will not
be placed in an unrecoverable condition, and will not result in a
radiological release that adversely affects the public, plant
personnel, or the environment. These goals, objectives, and criteria
are described in Chapter 1 and elsewhere in the standard. NFPA 805
allows the use of either a deterministic or performance-based approach
to achieve the performance goals, objectives, and criteria of Chapter
1. Subsequent chapters of the standard describe methodologies to be
used to establish the required fire protection systems and features,
including the analyses used to support the performance-based fire
protection design that fulfills these goals.
NFPA 805 requires the licensee to use a deterministic or
performance-based approach to assess whether the performance goals,
objectives, and criteria in Section 1.5 of the standard are met. The
methodologies for implementing these approaches are established in
Chapters 2 and 4 of NFPA 805. Chapter 3 of NFPA 805 provides certain
deterministic and administrative requirements for fire protection
systems and features that are not subject to the NFPA 805 performance-
based approach. The methodology in Chapter 2 describes how these
approaches are to be developed and implemented. The methodology in
Chapter 4 describes the process to be used to determine which fire
protection systems and features are required to achieve the performance
criteria outlined in Chapter 1.
NFPA 805 accomplishes the intent of the Appendix R, Section I,
requirements through the methodology in Chapter 4 of NFPA 805. That
methodology requires that a nuclear safety capability assessment be
performed that determines that one success path is maintained free of
fire damage from a single fire. The assessment may use either a
deterministic or a performance-based approach. The deterministic
approach requires protection for one success path of required cables
and equipment to achieve and maintain the nuclear safety performance
criteria in Chapter 1. The nuclear safety performance criteria is
considered to be satisfied when the protection scheme meets certain
deterministic criteria such as when a 3-hour fire barrier encapsulation
of one success path is provided. The performance-based approach
requires that, using the Chapter 2 methodology, information on targets,
damage thresholds, limiting conditions, and fire scenarios be used to
determine the protection scheme necessary to ensure the nuclear safety
success path(s) for required cables and equipment are maintained free
of fire damage to achieve the nuclear performance criteria in Chapter
1.
[[Page 33540]]
Chapter 3 of NFPA 805 accomplishes the requirements for general
fire protection program features described in Appendix R, Section II.A.
and the general fire prevention features described in Appendix R,
Section II.C. The defense-in-depth objectives described in Appendix R,
Section II, General Requirements, are incorporated in NFPA 805. The
defense-in-depth objectives of Appendix R, Section II, are (1) prevent
fires from starting; (2) detect rapidly, control, and extinguish
promptly those fires that do occur; and (3) provide protection for
structures, systems, and components important to safety so that a fire
that is not promptly extinguished by the fire suppression activities
will not prevent the safe shutdown of the plant. These defense-in-depth
objectives are stated in Section 1.2 of NFPA 805 and the methods to
accomplish them are specified in the standard as described below:
1. Prevention of fires is specified in Section 3.3 of NFPA 805 and
includes control of ignition sources, control of combustible and
flammable materials, use of noncombustible or fire resistant structural
materials, and control of cable construction and raceways.
2. Fire detection and suppression are required in Sections 3.4
through 3.11 of NFPA 805 and include on-site fire-fighting capability,
fire alarms, manual and fixed suppression systems, and passive fire
protection features.
3. Protection of SSCs important to achieve the nuclear safety
performance criteria is specified in Chapter 4 of NFPA 805. Chapter 4
establishes the methodology to determine the fire protection systems
and features required to achieve the performance criteria and specifies
that at least one success path to achieve the nuclear safety
performance criteria shall be maintained free of fire damage by a
single fire. The nuclear safety performance criteria specified in
Section 1.5 are: (1) Reactivity control, (2) inventory and pressure
control, (3) decay heat removal, (4) vital auxiliaries, and (5) process
monitoring.
The methodologies described in NFPA 805 Chapters 2 and 4 and the
fundamental fire protection program and design elements in Chapter 3
require a general fire hazards analysis similar to that described in
Appendix R, Section II.B. Appendix R, Section II.D, which describes
alternative or dedicated shutdown capability, is discussed later in
this section.
The NRC has evaluated Appendix R, Section III, Specific
Requirements, and determined that, with certain differences (e.g., cold
shutdown, alternate or dedicated shutdown, shutdown methods and
emergency lighting), NFPA 805 Chapter 3 and the methodologies in
Chapters 2 and 4 provide acceptable alternative criteria to the
specific fire protection requirements in Section III.
For example, Appendix R, Section III.A, Water supplies for fire
suppression systems, is the design criteria for fire suppression system
water supplies and it requires certain design features, such as the
duration of the water supply and configuration of the water sources, to
be met. NFPA 805 has similar requirements in Chapter 3 for water supply
and configuration that are acceptable alternatives to the requirements
in Appendix R.
Another example is Appendix R, Section III.K, Administrative
controls, which requires controls to govern the activities related to
the handling of combustible materials and ignition sources and govern
actions by emergency and general plant personnel. NFPA 805 has
requirements in Chapter 3 for administrative controls that are
acceptable alternatives to the requirements in Appendix R.
Appendix R, Section III.G, Fire protection of safe shutdown
capability, provides the deterministic requirements to ensure that one
train of systems necessary to achieve and maintain hot shutdown is free
of fire damage and systems necessary to achieve and maintain cold
shutdown can be repaired within 72 hours. The final rule (45 FR 76602;
November 19, 1980) that promulgated 10 CFR 50.48 and Appendix R, dated
November 19, 1980, stated that the objective for the protection of safe
shutdown capability is to ensure that at least one means of achieving
and maintaining safe shutdown conditions will remain available during
and after any postulated fire in the plant. NFPA 805 requires that, in
the event of a fire, the plant be able to achieve and maintain the fuel
in a safe and stable condition and that the plant is not placed in an
unrecoverable condition in lieu of the analyzed shutdown method
delineated in Section III.G. Specific criteria for the NFPA 805
conditions are provided in Section 1.5 of NFPA 805. These differences
in requirements for plant shut down result from the fact that NFPA 805
is performance-based rather than deterministic. The shutdown methods
delineated in Section III.G are not required by NFPA 805 because they
are not needed to achieve the performance criteria of NFPA 805.
However, NFPA 805, Chapter 4, requires that one success path necessary
to achieve and maintain the nuclear safety performance criteria be
maintained free of fire damage by a single fire. Therefore, NFPA 805
has a similar objective for the protection of safe shutdown via its
requirement of one success path. These minor differences from Appendix
R are acceptable because achieving the nuclear safety goals,
objectives, and performance criteria of NFPA 805 provide controls for
maintenance of the reactor fuel and the plant condition that ensure
adequate protection of public health and safety.
The criteria and methodologies contained in NFPA 805 provide
acceptable alternatives to the requirements in Appendix R, Sections I,
II, and III regarding fire protection features required to satisfy GDC
3.
In addition to the requirements of 10 CFR 50.48(b) and Appendix R,
the NRC reviewed the NFPA 805 fire protection criteria versus the
guidance in RG 1.189, ``Fire Protection for Operating Nuclear Power
Plants.'' Section C of RG 1.189, ``Regulatory Position,'' describes
eight elements of an acceptable fire protection program. The NRC review
determined that NFPA 805 provides adequately for each element. These
eight elements are:
1. Delineation of organization, staffing, and responsibilities.
2. Performance of a fire hazards analysis sufficient to ensure safe
shutdown functions and minimize radioactive material releases in the
event of a fire.
3. The limitation of damage to SSCs important to safety so that the
capability to safely shut down the reactor is ensured.
4. Evaluation of fire test reports and fire data to ensure they are
appropriate and adequate for ensuring compliance with regulatory
requirements.
5. Evaluation of compensatory measures for interim use for adequacy
and appropriate length of use.
6. Training and qualification of fire protection personnel
appropriate for their level of responsibility.
7. Quality assurance.
8. Control of fire protection program changes.
For example, element 3, limitation of damage to SSCs important to
safety so that the capability to safely shut down the reactor is
ensured, is addressed in NFPA Chapter 4. Chapter 4 of the standard
establishes methods to determine the fire protection needed to limit
fire damage to SSCs required to achieve the nuclear safety performance
criteria in Section 1.5 of NFPA 805 and specifies that the design and
qualification of those fire protection systems or features meet the
applicable requirements of Chapter 3. The criteria in the standard are
adequate to meet the intent of this element of RG 1.189.
[[Page 33541]]
NFPA 805 Differences With Respect to Appendix R
NFPA 805 does not explicitly include some requirements of Appendix
R. NFPA 805 has no deterministic requirements for cold shutdown and
emergency lighting, no provision for an alternative shutdown
capability, and allows the use of recovery actions. NFPA 805 requires
that the fuel be maintained in a safe and stable condition rather than
prescribing the requirement for hot shutdown, cold shutdown, or the
provisions for an alternate or dedicated shutdown. These differences
result from the fact that NFPA 805 is performance-based rather than
deterministic, with a performance goal to achieve a safe and stable
condition. Deterministic requirements for emergency lighting for
operation of safe shutdown equipment are not included in NFPA 805
because varying degrees of lighting and duration of lighting may be
implemented by a performance-based approach provided that the
performance goal to achieve a safe and stable condition can be
demonstrated and met. The use of feasible recovery actions are allowed
in NFPA 805 provided that the performance-based approach is used and
can demonstrate and meet the performance goal. Also, the additional
risk resulting from the use of recovery actions must be evaluated.
These differences from Appendix R are acceptable because the nuclear
safety performance criteria of NFPA 805 must be met in order to achieve
a safe and stable condition. Meeting the performance criteria ensures
adequate protection of public health and safety.
NFPA 805 includes some specific requirements that are not included
in Appendix R. For example, NFPA 805 applies during all phases of plant
operation including shutdown and degraded conditions. NFPA 805, Chapter
5, applies to plants that have permanently ceased operation and
requires that the fire protection plan specified in Chapter 3 of NFPA
805 be maintained. The application of fire protection criteria for all
phases of plant operation is more inclusive than 10 CFR 50.48(b) and
Appendix R, resulting in a more comprehensive fire protection program.
Appendix R, Section II.B, requires a fire hazards analysis to
determine the consequences of fire on the ability to minimize and
control the release of radioactivity to the environment. Similarly,
NFPA 805, Chapter 1, requires that radiation release goals, objectives,
and performance criteria be met. The radioactive release goal of NFPA
805 is to provide reasonable assurance that a fire will not result in a
radiological release that adversely affects the public, plant
personnel, or the environment. The NFPA 805, Chapter 1, Radioactive
Release Performance Criteria, requires that radiation release from the
effects of fire suppression activities shall be as low as reasonably
achievable and shall not exceed 10 CFR part 20 limits. NFPA 805,
Chapter 4, requires the evaluation for demonstrating how the criteria
are met. The NFPA 805 approach to radioactive release is more
comprehensive than 10 CFR 50.48(b) and Appendix R and is considered
adequate to ensure the protection of public health and safety.
Acceptability of NFPA 805 for Decommissioning Plants
The first paragraph of 10 CFR 50.48(f) is revised to include the
statement that a fire protection program that complies with NFPA 805 is
deemed to be acceptable for complying with the requirements of
paragraph (f). Section 50.48(f) requires licensees to maintain a fire
protection program to prevent, detect, control, and extinguish fires
that could result in a radiological hazard and to ensure that the risk
of fire-induced radiological hazards to the public, environment, and
plant personnel is minimized. Further, 10 CFR 50.48(f) requires
licensees to assess and revise the fire protection program throughout
the stages of decommissioning as the fire hazard threat changes and
allows licensees to make changes to the fire protection program if the
changes do not reduce the effectiveness of the fire protection program,
taking into account the decommissioning plant conditions and
activities.
The NRC reviewed NFPA 805, Chapter 5, and determined that it
requires a fire protection plan to be maintained throughout
decommissioning and permanent shutdown. It also specifies that the plan
maintain a fire protection program as specified by Section 3.1 of NFPA
805. The fire protection program specified in Section 3.1 requires that
fundamental fire protection program elements and minimum design
requirements be established and maintained as part of the plant fire
protection program. NFPA 805, Section 5.2, requires controls governing
the identification of fire hazards, fire prevention, fire detection,
fire fighting capability, and emergency response. Section 5.2 also
requires the maintenance of a fire protection program that is
commensurate with the fire hazards as decommissioning progresses. NFPA
805, Section 5.3, identifies specific fire protection program elements
and requires that the fire protection program elements be established
and maintained as decommissioning progresses after permanent shutdown.
As a plant progresses into decommissioning, the fire protection program
that meets the nuclear safety criteria in NFPA 805, Chapter 1, changes
because the fuel has been removed from the reactor and the reactor is
no longer operating. The focus of the fire protection program changes
to control fires that may cause the release of radioactivity, taking
into consideration changes in plant configuration, maintenance, and
activities as the plant progresses beyond permanent shutdown. Section
5.3, of NFPA 805, requires that the fire protection program be
maintained commensurate with these changes in fire hazards and the
potential for release of hazardous and radiological materials to the
environment. Because the NFPA 805 fire protection program requirements
for a decommissioning plant are technically equivalent to the
requirements of paragraph (f), the NRC considers that a fire protection
program that complies with NFPA 805 is acceptable for complying with
the requirements of paragraph (f).
Statement of Acceptability of 10 CFR 50.48(c) and NFPA 805
The NRC considered whether 10 CFR 50.48(c) provides requirements
and criteria for licensees to implement fire protection features for
certain generic issues referenced in 10 CFR 50.48(b) and as established
in Appendix R to 10 CFR 50, or as required by plant license conditions
resulting from NRC reviews of plant licenses to those features
established in Appendix R. The NRC reviewed the requirements in Chapter
3 of NFPA 805 for the establishment of fundamental fire protection
program elements and minimum design requirements; the performance
goals, objectives, and criteria in Chapter 1 of NFPA 805; the
methodology in Chapter 4 for identifying fire protection systems and
features required to meet the Chapter 1 performance criteria; and the
methodology in Chapter 2 for the implementation of deterministic or
performance-based approaches to establish those fire protection systems
and features. The NRC determined that NFPA 805 contains requirements
that address those generic issues referenced in 10 CFR 50.48(b) and
provides sufficient requirements and criteria for licensees to
implement fire protection features that satisfy GDC 3 with respect to
those issues. Therefore, the NRC determined that compliance with 10
[[Page 33542]]
CFR 50.48(c) is an acceptable alternative to compliance with 10 CFR
50.48(b) for plants licensed to operate before January 1, 1979, or the
fire protection license conditions for plants licensed to operate after
January 1, 1979.
In addition, the NRC reviewed the requirements in Chapter 5 for
licensees who have submitted the certifications required under 10 CFR
50.82(a)(1). The NRC considered the requirements in Chapter 5 to
continue to maintain the fire protection systems and features needed to
meet the performance criteria of Chapter 1, to continue to maintain a
fire protection plan as specified in Section 3.2 of NFPA 805, and the
criteria in Chapter 5 regarding issues applicable to a plant
progressing through decommissioning and into permanent shutdown. The
NRC determined that a fire protection program that complies with NFPA
805 meets the requirements for a fire protection program as specified
in 10 CFR 50.48(f).
Discussion of Provisions of the Rule
The following paragraphs discuss the bases for certain provisions
in this rule. The final rule provides for licensees to request a
license amendment that would permit them to maintain a fire protection
program that complies with NFPA 805, identifies seven exceptions to
NFPA 805, and provides a method for licensees to request to use risk-
informed, performance-based alternatives to provisions in NFPA 805.
Provision for Adoption of NFPA 805
In accordance with 10 CFR 50.48(c)(3)(i), a licensee may maintain a
fire protection program that complies with NFPA 805 as an alternative
to complying with paragraph (b) of this section for plants licensed to
operate before January 1, 1979, or the fire protection license
conditions for plants licensed to operate after January 1, 1979. The
licensee shall submit a request in the form of an application for
license amendment under Sec. 50.90. The application must identify any
orders and license conditions that must be revised or superseded, and
contain any necessary revisions to the plant's technical specifications
and the bases thereof.
Provisions for Exceptions to NFPA 805
The NRC identified provisions of the NFPA 805 Standard that were
determined to be unacceptable or inappropriate to endorse in this
rulemaking. A description of each exception and the bases for the
exception follows:
Life Safety and Plant Damage/Business Interruption Goals, Sec.
50.48(c)(2)(i) and (ii)
The Life Safety and Plant Damage/Business Interruption goals,
objectives, and criteria in Sections 1.3, 1.4, and 1.5 of NFPA 805 are
not endorsed in this rule. The Plant Damage/Business Interruption goal
to provide reasonable assurance that the potential economic
consequences of the risk of a fire are acceptable is not within the
regulatory responsibility of the NRC under the Atomic Energy Act of
1954, as amended, to provide for the common defense and security and to
protect the health and safety of the public. The Life Safety Goal
provides for protection of plant personnel (including essential
personnel) from the effects of a fire but is not fully within the
regulatory responsibility of the NRC. Those portions of the Life Safety
Goal that are within the scope of NRC regulatory responsibility, such
as adequate protection for essential personnel, are required elsewhere
in the standard. Therefore, the NRC is not endorsing the NFPA 805 Life
Safety or Plant Damage/Business Interruption Goals.
Feed and Bleed, Sec. 50.48(c)(2)(iii)
The NRC does not accept the use of a high-pressure charging/
injection pump coupled with the pressurizer power operated relief
valves (PORVs) as the sole fire protected shutdown path for maintaining
reactor coolant inventory, pressure control, and decay heat removal
capability (i.e., feed-and-bleed) for pressurized water reactors
(PWRs). Reliance on feed-and-bleed as the sole method for achieving
these criteria does not provide sufficient defense-in-depth. Therefore,
feed-and-bleed as the sole means of demonstrating achieving the nuclear
safety performance criteria in Section 1.5.1(b) and (c) is not
permitted.
Uncertainty Analysis, Sec. 50.48(c)(2)(iv)
The uncertainty analysis required by Section 2.7.3.5 of the
standard is not required for the deterministic approach because
conservatism is included in the deterministic criteria.
Existing Cables, Sec. 50.48(c)(2)(v)
Section 3.3.5.3 of the standard provides that electric cable
construction shall comply with a flame propagation test acceptable to
the AHJ. For this rulemaking, the NRC is requiring compliance with 10
CFR 50.48(c)(2)(v), which provides for the use of flame-retardant
coatings on electric cables or an automatic fixed fire suppression
system in lieu of installing cables meeting an acceptable flame
propagation test. The electrical flame propagation test compliance was
put in place after some licensees had installed cabling that could not
be qualified to a flame propagation test. The NRC determined that
flame-retardant coatings or a fixed fire suppression system provided an
acceptable level of protection for these licensees (see Appendix A to
BTP APCSB 9.5-1). Licensees should have these configurations as part of
their licensing basis, where applicable. This provision, therefore,
carries forward a previously accepted alternative to meeting a flame
propagation test.
Additionally, the italicized exception to Section 3.3.5.3 of the
standard is not endorsed because it would allow cables that did not
comply with an acceptable flame propagation test to remain in place in
a reactor plant without mitigation even though they were not approved
in the licensing basis. Cables that do not meet this requirement could
contribute to failure of operating or shutdown systems and the
contribution to risk has not been calculated or approved. The criteria
that electric cable constructions should pass flame propagation testing
has been in NRC guidance since 1976 (Appendix A to BTP APCSB 9.5-1).
Water Supply and Distribution, Sec. 50.48(c)(2)(vi)
The italicized exception to Section 3.6.4 of the standard is not
endorsed. The exception would allow a licensee to have a
``provisional'' manual fire-fighting standpipe/hose station system in
place of seismically qualified standpipes and hose stations even though
it was not approved in the licensing basis. The NRC interprets Section
3.6.4, which is one of the fire protection elements and minimum design
requirements of Chapter 3, as requiring seismically qualified
standpipes and hose stations in all areas containing systems and
components needed to perform the nuclear safety functions in the event
of a safe shutdown earthquake. NRC guidance to supply water at least to
standpipes and hose connections for manual fire-fighting in areas
required for safe plant shutdown in the event of an earthquake, and
that the standpipe system serving such hose stations be analyzed for
seismic loading to assure system pressure integrity, has been in
existence since 1976. Therefore, the NRC considers seismically
qualified standpipes and hose stations of such importance that
licensees who wish to use the exception to Section 3.6.4 in NFPA 805
must obtain NRC review and
[[Page 33543]]
approval in accordance with Sec. 50.48(c)(2)(vii).
Performance-Based Methods, Sec. 50.48(c)(2)(vii)
The prohibition in Section 3.1 of NFPA 805 that does not permit the
use of performance-based methods for the Chapter 3 fundamental fire
protection program elements and minimum design criteria is not
endorsed. The NRC takes this exception in order to provide licensees
greater flexibility in meeting the fire protection program elements and
minimum design requirements of Chapter 3 by the use of performance-
based methods (including the use of risk-informed methods) described in
the NFPA 805 standard. This approach is acceptable to NRC because the
rule requires NRC review and approval prior to the licensee's use of
those methods, and the rule sets forth criteria for evaluating the
acceptability of the licensee's proposed use of performance-based
methods in meeting the fire protection program elements and minimum
design requirements.
Alternatives to Compliance With NFPA 805, Sec. 50.48(c)(4)
The final rule provides licensees the flexibility of requesting,
via a license amendment, to use risk-informed or performance-based
alternatives that deviate from compliance with NFPA 805. The NRC
recognizes that licensees may propose acceptable approaches that are
not encompassed by the criteria in NFPA 805. Therefore, the NRC is
including a provision for requesting such approaches in the rule.
However, to ensure adequate protection of public health and safety, the
NRC is requiring that licensees obtain NRC review and approval to use
those methods, and is providing criteria in Sec. 50.48(c)(4) for
review of their acceptability.
III. Comment Resolution on Proposed Rule
The 75-day public comment period for the proposed rule ended
January 15, 2003. Comments were received from organizations and
individuals. Copies of the comments are available for public inspection
and copying for a fee at the Commission's Public Document Room, One
White Flint North, 11555 Rockville Pike (first floor), Rockville,
Maryland. The comments were submitted by an individual, an individual
representing a public interest group, a utility with a nuclear reactor,
two nuclear utility groups each representing six plants with nuclear
reactors, a law firm, a law firm representing several utilities, and
NEI. Most commenters supported the proposed rule and made
recommendations to enhance or modify elements of the rule. One
commenter opposed adoption of the proposed rule.
In the following paragraphs, the NRC discusses the resolution of
the public comments by topic.
Need for License Amendment
A commenter suggested that the NRC amend 10 CFR 50.55a, ``Codes and
standards,'' to add a paragraph referencing NFPA 805, which could then
be referenced in 10 CFR 50.48 as an optional alternative approach. The
commenter stated that this approach would negate the need for licensees
to obtain a license amendment in order to adopt NFPA 805 or approved
alternative approaches under the provisions of 10 CFR 50.55a(c)(3). The
commenter also stated that the process for obtaining NRC approval of
alternate methods should not require a license amendment.
The NRC does not agree that amending 10 CFR 50.55a would negate the
need for a license amendment in order for licensees to adopt NFPA 805.
The NRC believes that, even if Sec. 50.55a were revised as suggested
by the commenter, it would not negate the need to change the license.
To adopt NFPA 805, technical specifications and license conditions will
need to be changed and such changes are amendments to the license.
Regarding the use of methods, licensees may use methods such as fire
modeling and fire PSAs without prior NRC review and approval. However,
such use is at the licensee's risk and is subject to subsequent
inspection by the NRC.
Risk-Informed Methodology
A commenter stated that NFPA 805 does not include risk-informed
methodologies such as NEI 00-01, ``Methodology for Post-Fire Circuit
Analysis,'' therefore the regulatory text or implementing guidance
should recognize the use of risk-informed methodologies to address the
appropriate issues.
The NRC agrees that NFPA 805 does not include risk-assessment
methods. Although fire models and fire PSA methods have been developed,
technical issues remain regarding their acceptability for the full
range of decisions in risk-informed regulation by industry.
Degraded Conditions
A commenter observed that the description of NFPA 805 in the
Federal Register Notice (FRN) for the proposed rule states that the
standard specifies the minimum fire protection requirements for
existing light water reactors during all modes (``phases'' in NFPA 805)
of plant operation, including shutdown, degraded conditions, and
decommissioning. The commenter stated that fires should not be
postulated with degraded conditions unless the fire and the degraded
condition have a common cause.
The NRC disagrees with this comment. In citing the paragraph from
Section 1.1, ``Scope,'' of the standard, the NRC was identifying the
modes or phases of operation for which NFPA 805 was applicable. The NRC
believes the wording is appropriate as it correctly identifies the
scope of NFPA 805. However, the NRC was not imposing a requirement that
a degraded condition be postulated in addition to a fire for purposes
of analyses.
Existing Cables
A commenter stated that the italicized exception in Section 3.3.5.3
of NFPA 805 allowed existing cables in place prior to adoption of the
standard to remain as is and argued that leaving these cables in place
was consistent with the ``safe today, safe tomorrow'' philosophy.
Therefore, the exception should be retained in the rule.
The NRC disagrees with the suggestion that the italicized exception
in Section 3.3.5.3 of NFPA 805 be retained in the rule because it would
allow existing electrical cable which does not comply with a flame
propagation test acceptable to the NRC to remain as is even if the
existing license basis required the cables to be qualified.
Use of Feed-and-Bleed
A commenter agreed with the NRC that feed-and-bleed is one
available flow path to achieve and maintain safe shutdown but should
not be considered the ``preferred'' or ``sole'' path. However, the
commenter felt that feed-and-bleed should be considered as a viable
path for risk calculations.
The NRC agrees that feed-and-bleed may be used in risk
calculations. However, as previously noted, feed-and-bleed should not
be the sole path.
Regarding Sec. 50.48(c)(2)(iii) of the proposed rule, a commenter
noted that, ``This paragraph does not accept the use of a high-pressure
charging/injection pump coupled with the pressurizer PORVs as the sole
fire protected shutdown path * * *.'' The commenter stated that feed-
and-bleed should be considered as one of the multiple methods when used
in a risk-informed analysis of safe shutdown capability.
The NRC agrees with this comment. The purpose of Sec.
50.48(c)(2)(iii) is to identify that this path is not to be relied
[[Page 33544]]
on as a sole fire protected shutdown path.
Previously Approved Licensing Basis
A commenter asserted that licensees may bring forward portions of
their existing licensing basis or design configuration as alternatives
to the Chapter 3 fundamental elements when adopting NFPA 805. The
commenter stated that it is the licensee's responsibility to maintain
the plant licensing basis, but the burden of proof is the NRC's if the
NRC suggests that the licensing basis was not previously approved.
The NRC disagrees with the comment about the burden of proof.
Because it is the licensee's responsibility to maintain the plant
licensing basis, the burden of proof for previous approval is the
licensee's. The NRC notes that this is the existing inspection and
enforcement position which is generally applicable when a licensee
claims that the NRC has previously approved a licensee commitment.
A commenter asked if the discussion under Sec. 50.48(c)(3)(i)
meant that existing approved exemptions remain valid under NFPA 805 and
whether the licensee needed to identify that the associated safety
evaluation remained in effect.
The NRC's position is that existing exemptions remain valid after
transition to NFPA 805 as indicated in Section 3.1 of the standard, if
not otherwise revoked by the NRC as part of the initial approval to
transition to NFPA 805. The licensee's analysis of the facility to
perform the transition to NFPA 805 should include a review of fire
protection exemptions in effect at the time of application. The NRC
will deny the application if the NRC determines that the licensee does
not address the continued validity of any exemption in effect at the
time of application. As stated in Sec. 50.48(c)(3)(i), licensees must
identify any orders or license conditions to be revised or superseded.
Burden Discussion
A commenter recommended that the text in the statement of
considerations (SOC) for the proposed rule on ``Unnecessary Burden'' be
replaced with the following, ``Licensee adoption of the proposed rule
or use of the techniques in the rule is expected to reduce unnecessary
regulatory burdens by enabling licensees to cost-effectively adopt safe
alternatives to overly conservative deterministic requirements.''
NRC agrees that the rule provides licensees with the flexibility to
adopt performance-based alternatives to existing prescriptive
requirements and thus reduce unnecessary regulatory burden. The text of
the final rule SOC has been modified accordingly.
Licensee Impact
A commenter stated that the discussion on licensee impact in the
SOC should identify the primary impacts on licensees and that
characterizing the impacts as ``significant'' is not accurate and
should be deleted. The commenter provided a list of the primary impacts
expected and stated that they should be reflected in the FRN for the
final rule.
The NRC evaluated the primary impacts identified in the comment and
agreed that they are appropriate and should be included in the
discussion on licensee impact. The NRC modified the final rule
discussion to reflect this comment. The NRC does not agree that the
term significant is inaccurate because the analysis required by the
final rule is expected to be approximately 11,250 person-hours per
licensee.
Appendices
A commenter stated that, although NRC indicated in the SOC that it
intended to allow licensees to adopt NFPA 805 including Appendices B, C
and D the proposed language for 10 CFR 50.48(c) and 10 CFR 50.48(f)
does not specifically adopt the appendices. The commenter also stated
that the language in Appendices B, C, and D, was non-mandatory and that
the NRC would need to develop additional guidance as to how the
language of the appendices would be made mandatory. Another commenter
noted that Appendices C and D of NFPA 805 are not methodologies but
descriptions of attributes of methodologies.
The NRC agrees with the comment that the proposed rule did not
incorporate Appendices B, C, and D by reference and that these
appendices are not part of the standard. The NRC does not endorse the
appendices in this rule and expresses no position as to their
acceptability for use. However, licensees may, at their discretion and
risk, use the appendices subject to subsequent NRC inspection. Further,
the NRC agrees with the comment that Appendices C and D are not
methodologies but are considered to be guidance for application of fire
modeling or fire probabilistic safety assessment respectively.
Seismic Standpipes and Hose Stations
A commenter stated that the italicized exception to Section 3.6.4
of NFPA 805, which requires that provisions be made to supply water to
standpipes and hose stations for manual fire suppression in the event
of a safe shutdown earthquake (SSE), should be endorsed in the rule.
The exception would allow provisions to restore a water supply and
distribution system for manual fire-fighting purposes following an SSE.
The NRC does not agree that the exception should be endorsed
because it would allow licensees to use alternate provisions to
seismically qualified standpipes and hose stations even if the
licensing basis requires seismically qualified standpipes and hose
stations. Licensees with approved exemptions or deviations or whose
licensing basis does not require seismically qualified standpipes and
hose stations may comply with their existing licensing basis.
A commenter noted that Appendix A to BTP APCSB 9.5-1 did not
require seismically qualified standpipes and hose stations for
operating plants and plants with construction permits issued prior to
July 1, 1976.
NRC agrees that Appendix A to BTP APCSB 9.5-1 made separate
provisions for operating plants and plants with construction permits
issued prior to July 1, 1976, and did not require seismically qualified
standpipes and hose stations for those plants. Therefore, the
requirement in Section 3.6.4 of NFPA 805 is not applicable to licensees
with nonseismic standpipes and hose stations previously approved in
accordance with Appendix A to BTP APCSB 9.5-1.
Use of NFPA 805 Methods by Other Licensees
A commenter stated that licensees who do not adopt NFPA 805 should
not be precluded from using risk tools from NFPA 805.
The NRC agrees with the comment. However, licensees not adopting
NFPA 805 in accordance with the final rule are not covered by the
provisions for transitioning to NFPA 805. Such licensees who wish to
use the risk tools in NFPA 805 will need to separately determine if
their existing licensing basis would permit the use of such tools, and
take appropriate action as necessary to change their licensing basis.
Approaches Used in Different Fire Areas
A commenter asked whether, in light of the fact that the rule is
not intended to be implemented on a partial or selective basis, the
NFPA 805 deterministic approach can be selected for one fire area and
the performance-based approach for another.
[[Page 33545]]
Chapter 2 of the standard requires a licensee to select a
deterministic or a performance-based approach to determine how to meet
the performance criteria that apply to each fire area. Thus, Chapter 2
allows the use of different approaches for different fire areas.
However,Chapter 2 does not allow NFPA 805 to be only partially
implemented.
Meaning of the Term ``Element''
A commenter stated that the word ``element'' in the discussion of
plant change evaluations (Section 2.2.9 of the standard) should be
changed to ``attribute'' to be consistent with language or terminology
used in NFPA 805, Section 3.1. The term is used in Sections 2.2.1,
2.2.9, and 2.4.4 and Figure 2.2 of Chapter 2.
The NRC does not agree that the word ``element'' should be changed
in Section 2.2.9 of the standard. In Chapter 2, the term ``element''
includes the fundamental elements of the fire protection program
described in Chapter 3 of the standard (Section 2.2.1). Fundamental
elements are necessary components of an acceptable fire protection
program. Attributes are features or characteristics of the fundamental
elements and may vary based on the plant licensing basis. Section 3.1
states that previously approved alternatives from the fundamental
protection program attributes described in Chapter 3 take precedence
over the requirements contained in Chapter 3. Therefore, Section 2.2.9
applies to previously approved program elements as well as previously
approved attributes and the terminology in Section 2.2.9 is
appropriate.
Additional Issue for Public Comment
The NRC requested public comment on whether a licensee is likely to
revert to their previous licensing basis after being approved to use
NFPA 805 and, if they did, would a license amendment be required to
revert to their previous compliance basis. Two commenters stated that
licensees were not likely to revert to their previous status because
the regulatory environment under the requirements of NFPA 805 would be
more flexible. The commenters also stated that a license amendment
would be required to revert to the previous licensing basis after being
approved to use NFPA 805.
The NRC has determined that the final rule need not include
provisions governing the process for reversion from NFPA 805 to a
licensee's former fire protection licensing basis, because it is
unlikely that such reversions will occur.
Regulatory Analysis Burden Estimate, Problem Statement, and Estimated
Consequences
A commenter stated that the NRC estimate of 20,000 to 65,000
person-hours needed for the initial plant-wide analysis for each
licensee was excessive by a factor of three and should be revised.
The NRC agrees with this comment. The estimate of 20,000 to 65,000
person-hours was for four plants per year. The NRC estimate for the
initial analysis for one plant is 11,250 person-hours. The NRC
clarified the Regulatory Analysis and the OMB statement to state that
the hours shown were an annualized estimate of four plants adopting
NFPA 805.
A commenter noted that the Statement of the Problem section of the
Regulatory Analysis states that the ``alternative regulatory structure
would potentially reduce the number and complexity of future licensee
exemption or deviation requests * * *'' The commenter stated that this
section is inconsistent with the Alternatives section which states that
use of the NFPA 805 methods would preclude the need for exemptions or
deviations. The commenter stated that the text should be revised.
The NRC does not agree with this comment. The text in the
Alternatives section of the Regulatory Analysis states that licensees
may use approaches and methods contained in NFPA 805 rather than
submitting an exemption or deviation request. Thus, use of the NFPA 805
methods should reduce the need for exemption or deviation requests.
This text is consistent with the text in the Statement of the Problem
section.
A commenter stated that the wording in the Estimated Consequences
section suggests that fire protection features no longer required will
be removed. The commenter stated that such features will likely be
``abandoned in place'' or continued to be used as the licensee
determines. The NRC agrees with this comment and has revised the
section to indicate that fire protection features no longer required
may continue to be used, ``abandoned in place,'' or removed at the
discretion of the licensee.
One commenter stated that the NRC discussion in the Estimated
Consequences section did not follow guidance in NUREG/BR-0058, Revision
3, ``Regulatory Analysis Guidelines of the U.S. Nuclear Regulatory
Commission,'' in that NRC had not adequately demonstrated that the cost
savings attributed to the action (in the proposed rule) would be
substantial enough to justify taking the action. Further, the commenter
stated that the cost savings calculation should be based on an
assumption that all licensees will take advantage of the change as
noted in Section 2.2 of the NUREG. The commenter noted that the NRC had
not included reporting and recordkeeping costs in the regulatory
analysis.
Based on this comment, the NRC reviewed the draft Regulatory
Analysis and the draft Office of Management and Budget (OMB) statement
for recordkeeping and reporting costs and determined that the person-
hour estimates shown were for four plants adopting NFPA 805 annually,
rather than a per-plant figure. Hence the number of hours shown as
required was high by a factor of four for that of an individual plant.
The NRC clarified the Regulatory Analysis and the OMB statement to
state that the hours shown were an annualized estimate of 4 plants
adopting NFPA 805. The NRC stated in the draft Regulatory Analysis that
it was not possible to estimate the cost savings per plant as the
savings would vary significantly for each plant. However, for some
plants the savings in reduced downtime and spare parts maintenance
could be several times the cost of adopting NFPA 805; therefore, for
these plants the action is justified. Plants that do not adopt NFPA 805
are not affected.
The NRC based its cost calculations on an estimate of the number of
plants likely to adopt NFPA 805 rather than on all plants. This
approach is acceptable because NRC does not expect all plants to adopt
NFPA 805. Industry estimates that approximately 25 plants may adopt
NFPA 805 and NRC used that estimate in its calculations. Plants that do
not adopt NFPA 805 are not affected. The NRC has revised the Regulatory
Analysis to include reporting and recordkeeping costs.
Later Versions of NFPA 805
A commenter stated that the proposed rule should allow for the
voluntary adoption of later versions of NFPA 805, unless NRC notifies
licensees that a specific revision to NFPA 805 is not to be used. The
commenter suggested language to be used in the rule for this purpose.
The NRC may not legally provide regulatory approval of future
versions of NFPA 805 by rulemaking, because the NRC has no basis for
determining the acceptability of all future versions of NFPA 805.
[[Page 33546]]
Other Comments
1. Comments on Implementation and Inspection Issues
A commenter requested that NRC consider skipping the first post-
transition triennial inspection in reliance on the extensive program
review being conducted by each licensee.
The NRC agrees that the inspection program should recognize the
extent of the fire protection program review that would be conducted by
the licensee. The NRC is considering alternatives to the triennial
inspection or possibly modifying the focus of the triennial inspection
to reflect the programmatic review performed by plants transitioning to
NFPA 805.
A commenter suggested that, as has been done for other rules, the
NRC should exercise enforcement discretion for noncompliances
identified during the transition to the new fire protection
requirements.
The NRC agrees with the comment and is requesting Commission
permission to allow enforcement discretion for noncompliances
identified during the transition to the new requirements. This action
would encourage licensees to self-identify problems for placement in
their corrective action programs.
A commenter asserted that the NRC should conform inspection
guidance and the process for resolving noncompliances to the risk-
informed, performance-based methodology in the new rule.
The NRC agrees with this comment and will conform the inspector
guidance and the process for resolving noncompliances to the risk-
informed, performance-based methods in the rule, for those licensees
that transition to NFPA 805. No change will occur for licensees that
continue to comply with their existing fire protection licensing basis.
A commenter suggested that the NRC follow the inspection practice
for the American Society of Mechanical Engineers (ASME) Boiler and
Pressure Vessel Code and adopt a 10-year inspection cycle.
The NRC believes that the frequency appropriate for NRC inspection
of fire protection programs differs significantly from the frequency
appropriate for licensee inspection of piping and supports conducted
under 10 CFR 50.55a, which references requirements in the ASME Boiler
and Pressure Vessel Code. A significant difference is that Sec. 50.55a
itself establishes a 10-year interval for licensee conduct of inservice
inspection and inservice testing under a fixed version of the ASME Code
edition and addenda. Whereas, the greater frequency of NRC inspections
of licensee fire protection programs is appropriate because of the
likelihood for changes to plant configurations, procedures, and
practices affecting fire protection programs to occur more often.
Accordingly, the NRC does not intend to change the inspection
frequency.
A commenter suggested that the NRC exercise enforcement discretion
to eliminate the need to come into compliance with deviations from
current licensing basis requirements if compliance will be attained by
transitioning to the new requirements under NFPA 805.
The NRC is requesting Commission permission to allow enforcement
discretion during the transition period to the new requirements. If
enforcement discretion is implemented, licensees would need to take
appropriate compensatory actions for any identified noncompliance and
to place the noncompliance in the corrective action program. Corrective
actions may be to restore compliance with existing requirements or to
implement a performance-based approach that meets the requirements of
NFPA 805.
2. Comments on the Process for Adopting NFPA 805
A commenter suggested that the final rule define the scope of
fundamental attributes broadly enough to encompass current fire
protection programs and adopt a simple and predictable process for
finding that fundamental attributes have been previously approved by
the NRC.
The NRC disagrees with the commenter's suggestion that the final
rule should define the scope of fundamental attributes to encompass
current fire protection programs. The NRC considers Chapter 3 of NFPA
805 sufficient to describe the fundamental fire protection elements for
a risk-informed, performance-based fire protection program using NFPA
805. The attributes of current fire protection program elements vary
from plant-to-plant and determining generic fundamental fire protection
elements applicable to the full range of as-yet-unknown risk-informed
or deterministic approaches is beyond the scope of this rulemaking.
Section 3.1 of NFPA 805 provides that previously approved attributes of
a licensee's current fire protection program may be retained.
Therefore, licensees may evaluate previously approved attributes for
their plants and determine whether they wish to retain those
attributes. The NRC is working with industry to develop a predictable
process to be described in the implementing guidance document for
identifying previously approved attributes. The licensee is responsible
for maintaining its licensing basis including previous NRC approvals.
A commenter stated that the final rule should have a simple, swift
process for approving the transition license amendment.
The NRC believes the process described in the rule for approving
the license amendment is appropriate. The NRC expects that the
implementing guidance will provide additional guidance that will help
with the approval process.
3. Comments on the Acceptability of NFPA 805 as a Fire Protection
Program
Performance-Based Program. A commenter expressed concerns about
whether a risk-informed or performance-based fire-protection program
provides a sufficient level of protection of public health and safety
compared to existing deterministic requirements. The commenter noted
events where the industry experienced unexpected consequences from
methods for maintenance and testing, and cited events at Browns Ferry
and Davis-Besse as examples. The commenter also expressed a concern
that, in light of the terrorist attacks on the World Trade Center,
blast and fire standards should be deterministic.
The NRC disagrees with the comment. The NRC evaluated the NFPA 805
program and determined that, when implemented as an integrated whole,
NFPA 805 provides criteria for an acceptable fire protection program
and provides an acceptable level of protection of public health and
safety. This determination is based on a review of the program versus
regulatory requirements of GDC 3 and 10 CFR 50.48(a), as well as the
criteria for an acceptable fire protection program in RG 1.189, the
risk application methods criteria in RG 1.174, and the NFPA 805
criteria for the use of performance-based methods and risk information.
The NRC agrees that unexpected consequences may result from maintenance
and testing and notes that such consequences may occur whether under a
deterministic or a performance-based fire protection program. The
events at Browns Ferry and Davis-Besse emphasize the importance of
defense-in-depth and the maintenance of safety margins. Both of these
fundamental aspects of fire protection must be maintained under NFPA
805. Thus, the NRC believes that proper implementation of NFPA 805 will
be as
[[Page 33547]]
effective as the current deterministic-based requirements in providing
reasonable assurance of adequate protection with respect to fire
protection.
Regarding terrorist type of attacks, the NRC has taken action as a
result of the events that occurred at the World Trade Center and
continues to evaluate additional actions that may be appropriate.
Use of Fire Models. A commenter questioned the use of fire models
under NFPA 805 because of the uncertainty associated with them.
The NRC disagrees that fire models should not be used because of
the uncertainty associated with them. NFPA 805 provides for the use of
fire models to support performance-based approaches and gives
information on the use and application of fire modeling in Appendix C.
Section 2.4.1.2.2 of the standard provides that fire models must be
applied within the limitations of the fire model. Any uncertainty
associated with a fire model must be quantified and included, as
appropriate, in the performance-based approach. The NRC believes that
NFPA 805 provides appropriate requirements for use of fire models
relative to associated uncertainty.
Use of NEI 00-01. A commenter questioned whether industry document,
NEI 00-01, ``Guidance for Post-Fire Safe Shutdown Circuit Analysis,''
was sufficiently a ``consensus'' standard to be used in the NFPA 805
environment.
The NRC disagrees with the comment. The NRC has reviewed and
commented on NEI 00-01 throughout its development and is considering
endorsing NEI 00-01. If endorsed,NEI 00-01 will be a tool that
licensees may use to determine the risk significance of fire effects on
certain circuits. Such tools do not need to be consensus standards to
be used within the NFPA 805 structure.
IV. Section-by-Section Analysis
Section 50.48(c). National Fire Protection Standard NFPA 805
The final rule adds a new paragraph (c) to 10 CFR 50.48 that
permits nuclear power reactor licensees to voluntarily adopt NFPA 805,
with certain exceptions stated in the regulatory text, as an
alternative set of fire protection requirements for the operation of
light-water reactors. NFPA 805, if adopted by licensees, constitutes an
acceptable means for licensees of currently operating reactors to
comply with 10 CFR 50.48(a), and is an alternative to meeting their
existing fire protection requirements.
Section 50.48(c)(1). Approval of Incorporation by Reference
This paragraph states that NFPA 805, 2001 Edition, was approved for
incorporation by reference by the Director of the Federal Register. The
appendices to NFPA 805, which are not part of the standard, are not
incorporated by reference.
Section 50.48(c)(2). Exceptions, Modifications, and Supplementation of
NFPA 805
This paragraph states that references in Sec. 50.48 to NFPA 805
are to the 2001 Edition, with certain delineated exceptions,
modifications, and supplementation described in paragraphs (c)(2)(i)-
(vii) of the final rule.
Section 50.48(c)(2)(i). Life Safety Goal, Objectives, and Criteria
This paragraph provides that the Life Safety Goal, Objectives, and
Criteria of NFPA 805 Chapter 1 are not endorsed by the NRC.
Section 50.48(c)(2)(ii). Plant Damage/Business Interruption Goal,
Objectives, and Criteria
This paragraph provides that the Plant Damage/Business Interruption
Goal, Objectives, and Criteria of NFPA 805 Chapter 1 are not endorsed
by the NRC.
Section 50.48(c)(2)(iii). Use of Feed-and-Bleed
This paragraph provides that the use of a high-pressure charging/
injection pump coupled with the PORVs is not acceptable as the sole
fire-protected shutdown path for maintaining reactor coolant inventory,
pressure control, and decay heat removal capability (i.e., feed-and-
bleed) for PWRs.
Section 50.48(c)(2)(iv). Uncertainty Analysis
This paragraph provides that a licensee need not prepare an
uncertainty analysis in accordance with Section 2.7.3.5 when using a
deterministic approach as specified in Section 2.2.6 and Chapter 4 of
NFPA 805
Section 50.48(c)(2)(v). Existing Cables
This paragraph provides that in lieu of installing cables meeting
flame propagation tests as required by Section 3.3.5.3 of the standard,
a licensee may use either cables with a flame-retardant coating or an
automatic fixed fire suppression system to provide an equivalent level
of fire protection. In addition, the italicized exception to Section
3.3.5.3 is not endorsed.
Section 50.48(c)(2)(vi). Water Supply and Distribution
This paragraph provides that a ``provisional'' manual fire-fighting
standpipe/hose station system may not be used in place of seismically
qualified standpipes and hose stations unless previously approved in
the licensing basis. Licensees who wish to use the italicized exception
in Section 3.6.4 of NFPA 805 must submit a request for a license
amendment in accordance with paragraph (c)(2)(vii). However, because
the NRC considers seismically qualified standpipes and hose stations of
such importance, the NRC believes that licensees who wish to use the
exception in Section 3.6.4 of NFPA 805 via a license amendment may have
difficulty satisfying the three criteria in paragraph (c)(2)(vii).
Section 50.48(c)(2)(vii). Performance-Based Methods
This paragraph takes exception to the prohibition in Section 3.1 of
NFPA 805 to the use of performance-based methods (including the use of
risk-informed methods) for the fire protection program elements and
minimum design requirements in Chapter 3. The NRC included this
exception to allow licensees flexibility in meeting the fire protection
program elements and minimum design requirements in Chapter 3. However,
the NRC considers that the fire protection program elements and minimum
design requirements in Chapter 3 are not suited to the performance-
based approaches permitted in NFPA 805 on a generic basis, and that any
performance-based approaches for these program elements or minimum
design requirements should be approved on a plant-specific basis via a
license amendment. Licensees proposing such performance-based
approaches for the fire protection program elements and minimum design
requirements in Chapter 3 must submit an application for a license
amendment to the NRC in accordance with Sec. 50.48(c)(4). The Director
of the Office of Nuclear Reactor Regulation (NRR), or a designee, may
approve the application if the Director or designee determines that the
proposed performance-based approach:
(i) Satisfies the performance goals, performance objectives, and
performance criteria specified in NFPA 805 related to nuclear safety
and radiological release.
(ii) Maintains safety margins.
(iii) Maintains fire protection defense-in-depth (fire prevention,
fire detection, fire suppression, mitigation, and post-fire safe
shutdown capability).
[[Page 33548]]
Section 50.48(c)(3)(i)
This paragraph allows licensees to adopt NFPA 805 as an alternative
to complying with 10 CFR 50.48(b) or existing plant fire protection
license conditions. This paragraph describes the method by which a
licensee will submit their request to adopt NFPA 805. If the NRC
approves a licensee's request to use NFPA 805, the Director of NRR or
designee will issue a license amendment that: (1) Removes superseded
license conditions and (2) includes a license condition imposing the
use of NFPA 805 together with an implementation schedule. In addition,
if necessary, the NRC will issue an order revoking unnecessary and
superseded exemptions and orders.
Licensees who are approved under paragraph (c)(3)(i) to use NFPA
805 may return to compliance with paragraph (b) and their previous
licensing basis. However, each licensee must comply with all applicable
requirements, including submitting an application for a license
amendment, and, as applicable, a request for exemption if the licensee
wishes to reinstate a revoked exemption.
Section 50.48(c)(3)(ii)
This paragraph requires licensees to complete all of the Chapter 2
methodology (including evaluations and analyses) and to modify their
fire protection plan before making changes to the fire protection
program or to the plant configuration. This process ensures that the
transition to an NFPA 805 configuration is conducted in a complete,
controlled, integrated, and organized manner. This requirement also
precludes licensees from implementing NFPA 805 on a partial or
selective basis (e.g., in some fire areas and not others, or truncating
the methodology within a given fire area).
The evaluations and analyses process in Chapter 2 of NFPA 805
provides for the establishment of the fundamental fire protection
program, identification of fire area boundaries and fire hazards,
determination by analysis that the plant design satisfies the
performance criteria, identification of SSCs required to achieve the
performance criteria, conduct of plant change evaluations,
establishment of a monitoring program, development of documentation,
and configuration control. Chapter 2 of NFPA 805 also provides for the
use of a deterministic or performance-based approach to determine that
the performance criteria are satisfied and provides for the use of
tools such as engineering analyses, fire models, nuclear safety
capability assessments, and fire risk evaluations to support
development of these approaches. The methodology for the use of these
tools is established in Chapter 4 of NFPA 805.
Section 50.48(c)(4). Risk-Informed or Performance-Based Alternatives to
Compliance With NFPA 805
This paragraph provides licensees with a mechanism to obtain NRC
approval of alternatives to NFPA 805 including the use of performance-
based approaches for the fire protection program elements and minimum
design requirements in Chapter 3 of NFPA 805. The licensee's request
should be in the form of a license amendment request and demonstrate
that the licensee's proposed alternative satisfies the performance
goals, objectives, and criteria specified in NFPA 805 for nuclear
safety and radiological releases. The proposed alternative must also
maintain safety margins and fire protection defense-in-depth (fire
prevention, fire detection, fire suppression, mitigation, and post-fire
safe shutdown capability). Addressing these criteria allows the NRC to
determine that the alternative implements the performance goals,
objectives, and criteria in Chapter 1 and complies with the
requirements of GDC 3.
Section 50.48(f)
This paragraph provides that licensees who have permanently ceased
operations and submitted the certifications required by 10 CFR
50.82(a)(1) may maintain a fire protection program that complies with
NFPA 805 and that fire protection program will be deemed to be
acceptable for complying with the requirements of paragraph (f).
V. Availability of Documents
The NRC is making the documents identified below available to
interested persons through one or more of the following methods as
indicated.
Public Document Room (PDR). The NRC Public Document Room is located
at One White Flint North, 11555 Rockville Pike, Rockville, Maryland.
Rulemaking Web site (Web). The NRC's interactive Rulemaking Forum
Web site is located at http://ruleforum.llnl.gov. These documents may
be viewed and downloaded electronically via this Web site.
NRC's Public Electronic Reading Room (PERR). The NRC's public
electronic reading room is located at http://www.nrc.gov/reading-rm.html. The subject document may be accessed using the ADAMS accession
number (e.g.,
ML
) provided below.
The NRC staff contact. The NRC project manager for this rulemaking
in the Office of Nuclear Reactor Regulation is Joseph L. Birmingham.
Mr. Birmingham can be reached by telephone at (301-- 415-2829, or via
e-mail to [email protected].
----------------------------------------------------------------------------------------------------------------
Document PDR Web PERR NRC Staff
----------------------------------------------------------------------------------------------------------------
SECY-98-0058............................ X X ML992910106
SECY-98-0144............................ X X ML992880068
SECY-00-0009............................ X X ML003671923
SECY-00-0191............................ X X ML003742883
SRM dated 06/30/1998.................... X X ML003753120
SRM dated 03/01/1999.................... X ............ ML003753601
SRM dated 02/24/2000.................... X X ML003686350
Federal Register Notice................. X X ML040540680 X
Regulatory Analysis..................... X X ML040540542 X
Environmental Assessment................ X X ML033440262 X
Comments Received....................... X X ML023570335
Comments Received....................... X X ML030230288
Comments Received....................... X X ML030160870
Comments Received....................... X X ML030160873
Comments Received....................... X X ML030170147
Comments Received....................... X X ML030230293
Comments Received....................... X X ML030230345
Comments Received....................... X X ML030240260
----------------------------------------------------------------------------------------------------------------
[[Page 33549]]
VI. Voluntary Consensus Standards
The National Technology Advancement and Transfer Act of 1995,
Public Law 104-113, requires that Federal agencies use technical
standards that are developed or adopted by voluntary consensus
standards bodies, unless the use of such standards is inconsistent with
applicable law or otherwise impractical. Public Law 104-113 requires
Federal agencies to use industry consensus standards to the extent
practical, it does not require Federal agencies to endorse a standard
in its entirety. The law does not prohibit an agency from generally
adopting a voluntary consensus standard while taking exception to
specific portions of the standard if those provisions are deemed to be
``inconsistent with applicable law or otherwise impractical.''
Furthermore, taking specific exceptions furthers the Congressional
intent of Federal reliance on voluntary consensus standards because it
allows the adoption of substantial portions of consensus standards
without the need to reject the standards in their entirety because of
limited provisions which are not acceptable to the agency.
Under this final rule, the NRC is amending its regulations to
incorporate by reference the National Fire Protection Association
(NFPA) Standard 805, ``Performance-Based Standard for Fire Protection
for Light Water Reactor Electric Generating Plants, 2001 Edition,''
(NFPA 805), as excepted, as an alternative set of fire protection
requirements. NFPA 805 is a national consensus standard developed by
participants with broad and varied interests, in which all interested
parties (including the NRC and licensees of nuclear power plants)
participate.
In a staff requirements memorandum dated September 10, 1999, the
Commission indicated its intent that a rulemaking identify all portions
of an adopted voluntary consensus standard which are not adopted and to
provide a justification for not adopting such portions. The portions of
NFPA 805 which the NRC proposes not to adopt, or to partially adopt,
are identified in the preceding Section II. The justification for not
adopting portions of NFPA 805, as set forth in these statements of
consideration, satisfy the requirements of Section 12(d)(3) of Public
Law 104-113, Office of Management and Budget (OMB) Circular A-119, and
the Commission's direction in the staff requirements memorandum dated
September 10, 1999.
In accordance with the National Technology Transfer and Advancement
Act of 1995 and OMB Circular A-119, the NRC requested public comment
during the proposed rulemaking regarding whether other national or
international consensus standards could be endorsed as an alternative
to NFPA 805 and no alternative standard was identified.
VII. Finding of No Significant Environmental Impact: Availability
The Commission has determined under the National Environmental
Policy Act of 1969, as amended, and the Commission's regulations in
Subpart A of 10 CFR part 51, that this rule is not a major Federal
action significantly affecting the quality of the human environment
and, therefore, an environmental impact statement is not required.
Through its evaluation of the provisions and requirements of NFPA 805
for fire protection and prevention of radiological release, the NRC
determined that there would not be any significant radiological or
nonradiological impacts to the environment from implementation of the
NFPA 805 fire protection program. Under NFPA 805, the environment would
continue to be adequately protected because the methods used for fire
detection, suppression, and mitigation are the same as those used under
the existing fire protection requirements. Further, there will be no
change in the release of radiological or nonradiological effluents to
the environment from those releases expected under existing fire
protection programs.
This determination is based on an evaluation of the goals,
objectives, and performance criteria in NFPA 805. These criteria
provide for defense-in-depth to control fires; control of plant
reactivity, coolant inventory, and pressure; decay heat removal; vital
auxiliaries; and process monitoring to minimize radioactive releases.
The NRC has determined that the environmental impacts of the proposed
action, the no-action alternative, and an alternative in which the NRC
would develop its own risk-informed standard, were similar. Further,
the NRC determined that the proposed action does not involve the use of
any different resources than those considered in the current rule.
The NRC provided every State Liaison Officer a copy of the
environmental assessment and the proposed rule for this action and
requested their comments on the environmental assessment. No comments
were received from the State Liaison Officers and no changes were made
to the environmental assessment.
VIII. Paperwork Reduction Act Statement
This final rule contains information collection requirements that
are subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et
seq.). These requirements were approved by the Office of Management and
Budget, approval number 3150-0011.
There is a one-time burden to the public of 11,290 hours for each
licensee, who chooses to use NFPA 805, to complete the required one-
time plant-wide re-analysis of the reactor's fire protection systems,
equipment, features, and procedures, and to submit a letter of intent
to adopt NFPA 805. Send comments on any aspect of these information
collections, including suggestions for reducing the burden, to the
Records and FOIA/Privacy Services Branch (T-5 F52), U.S. Nuclear
Regulatory Commission, Washington, DC 20555-0001, or by Internet
electronic mail to [email protected]; and to the Desk Officer,
Office of Information and Regulatory Affairs, NEOB-10202, (3150-0011),
Office of Management and Budget, Washington, DC 20503.
Public Protection Notification
The NRC may not conduct or sponsor, and a person is not required to
respond to, a request for information or an information collection
requirement unless the requesting document displays a currently valid
OMB control number.
IX. Regulatory Analysis
The Commission has prepared a Regulatory Analysis on this
regulation. The analysis examines the costs and benefits of the
alternatives considered by the Commission. The analysis is available
for inspection at the NRC's Public Document Room, located at One White
Flint North, Room 01-F15, 11555 Rockville Pike, Rockville, Maryland.
The analysis is also available as indicated under the Availability of
Documents heading of the SUPPLEMENTARY INFORMATION section.
X. Regulatory Flexibility Certification
In accordance with the Regulatory Flexibility Act of 1980, 5 U.S.C.
605(b), the Commission certifies that this rule would not have a
significant economic impact on a substantial number of small entities.
This final rule would affect only the licensing and operation of
nuclear power plants. The companies that own these plants do not fall
within the definition of ``small entities'' found
[[Page 33550]]
in the Regulatory Flexibility Act or within the size standards
established by the NRC in 10 CFR 2.810.
XI. Backfit Analysis
The NRC has determined that a backfit analysis is not required for
this final rule, because the rule does not involve any provisions that
would impose backfits as defined in 10 CFR 50.109(a)(1). The final rule
establishes voluntary alternative fire protection requirements for
licensees with construction permits prior to January 1, 1979 (all
existing light-water reactor plants). Licensees may adopt NFPA 805 as
an alternative set of fire protection requirements by submitting a
license amendment request. However, current licensees may continue to
comply with existing requirements. Any additional burden incurred by
adopting NFPA 805 would be at the licensee's discretion. The final rule
does not impose any new requirements and, therefore, does not
constitute a backfit as defined in 10 CFR 50.109(a)(1).
XII. Small Business Regulatory Enforcement Fairness Act
In accordance with the Small Business Regulatory Enforcement
Fairness Act of 1996, the NRC has determined that this action is not a
major rule and has verified this determination with the Office of
Information and Regulatory Affairs of OMB.
List of Subjects in 10 CFR Part 50
Antitrust, Classified information, Criminal penalties, Fire
protection, Incorporation by reference, Intergovernmental relations,
Nuclear power plants and reactors, Radiation protection, Reactor siting
criteria, and Reporting and recordkeeping requirements.
0
For the reasons given in the preamble and under the authority of the
Atomic Energy Act of 1954, as amended; the Energy Reorganization Act of
1974, as amended; and 5 U.S.C. 552 and 553, the NRC is adopting the
following amendments to 10 CFR part 50.
PART 50--DOMESTIC LICENSING OF PRODUCTION AND UTILIZATION
FACILITIES
0
1. The authority citation for 10 CFR part 50 continues to read as
follows:
Authority: Secs. 102, 103, 104, 105, 161, 182, 183, 186, 189, 68
Stat. 936, 937, 938, 948, 953, 954, 955, 956, as amended, sec. 234,
83 Stat. 444, as amended (42 U.S.C. 2132, 2133, 2134, 2135, 2201,
2232, 2233, 2236, 2239, 2282); secs. 201, as amended, 202, 206, 88
Stat. 1242, as amended, 1244, 1246 (42 U.S.C. 5841, 5842, 5846).
Section 50.7 also issued under Pub. L. 95-601, sec. 10, 92 Stat.
2951, (42 U.S.C. 5841) as amended by Pub. L. 102-486, sec. 2902, 106
Stat. 3123 (42 U.S.C. 5851). Section 50.10 also issued under secs.
101, 185, 68 Stat. 955, as amended (42 U.S.C. 2131, 2235); sec. 102,
Pub. L. 91-190, 83 Stat. 853 (42 U.S.C. 4332). Sections 50.13,
50.54(dd), and 50.103 also issued under sec. 108, 68 Stat. 939, as
amended (42 U.S.C. 2138). Sections 50.23, 50.35, 50.55, and 50.56
also issued under sec. 185, 68 Stat. 955 (42 U.S.C. 2235). Sections
50.33a, 50.55a and Appendix Q also issued under sec. 102, Pub. L.
91-190, 83 Stat. 853 (42 U.S.C. 4332). Sections 50.34 and 50.54 also
issued under sec. 204, 88 Stat. 1245 (42 U.S.C. 5844). Sections
50.58, 50.91, and 50.92 also issued under Pub. L. 97-415, 96 Stat.
2073 (42 U.S.C. 2239). Section 50.78 also issued under sec. 122, 68
Stat. 939 (42 U.S.C. 2152). Sections 50.80-50.81 also issued under
sec. 184, 68 Stat. 954, as amended (42 U.S.C. 2234). Appendix F also
issued under sec. 187, 68 Stat. 955 (42 U.S.C. 2237).
0
2. In Sec. 50.48, paragraph (c) is added and the introductory text of
paragraph (f) is revised to read as follows:
Sec. 50.48. Fire protection.
* * * * *
(c) National Fire Protection Association Standard NFPA 805.
(1) Approval of incorporation by reference. National Fire
Protection Association (NFPA) Standard 805, ``Performance-Based
Standard for Fire Protection for Light Water Reactor Electric
Generating Plants, 2001 Edition'' (NFPA 805), which is referenced in
this section, was approved for incorporation by reference by the
Director of the Federal Register pursuant to 5 U.S.C. 552(a) and 1 CFR
part 51. Copies of NFPA 805 may be purchased from the NFPA Customer
Service Department, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA
02269-9101 and in PDF format through the NFPA Online Catalog
(www.nfpa.org) or by calling 1-800-344-3555 or (617) 770-3000. Copies
are also available for inspection at the NRC Library, Two White Flint
North, 11545 Rockville Pike, Rockville, Maryland 20852-2738, and at the
NRC Public Document Room, Building One White Flint North, Room O1-F15,
11555 Rockville Pike, Rockville, Maryland 20852-2738. Copies are also
available at the National Archives and Records Administration (NARA).
For information on the availability of this material at NARA, call
(202) 741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html.
(2) Exceptions, modifications, and supplementation of NFPA 805. As
used in this section, references to NFPA 805 are to the 2001 Edition,
with the following exceptions, modifications, and supplementation:
(i) Life Safety Goal, Objectives, and Criteria. The Life Safety
Goal, Objectives, and Criteria of Chapter 1 are not endorsed.
(ii) Plant Damage/Business Interruption Goal, Objectives, and
Criteria. The Plant Damage/Business Interruption Goal, Objectives, and
Criteria of Chapter 1 are not endorsed.
(iii) Use of feed-and-bleed. In demonstrating compliance with the
performance criteria of Sections 1.5.1(b) and (c), a high-pressure
charging/injection pump coupled with the pressurizer power-operated
relief valves (PORVs) as the sole fire-protected safe shutdown path for
maintaining reactor coolant inventory, pressure control, and decay heat
removal capability (i.e., feed-and-bleed) for pressurized-water
reactors (PWRs) is not permitted.
(iv) Uncertainty analysis. An uncertainty analysis performed in
accordance with
Section 2.7.3.5 is not required to support deterministic approach
calculations.
(v) Existing cables. In lieu of installing cables meeting flame
propagation tests as required by Section 3.3.5.3, a flame-retardant
coating may be applied to the electric cables, or an automatic fixed
fire suppression system may be installed to provide an equivalent level
of protection. In addition, the italicized exception to Section 3.3.5.3
is not endorsed.
(vi) Water supply and distribution. The italicized exception to
Section 3.6.4 is not endorsed. Licensees who wish to use the exception
to Section 3.6.4 must submit a request for a license amendment in
accordance with paragraph (c)(2)(vii) of this section.
(vii) Performance-based methods. Notwithstanding the prohibition in
Section 3.1 against the use of performance-based methods, the fire
protection program elements and minimum design requirements of Chapter
3 may be subject to the performance-based methods permitted elsewhere
in the standard. Licensees who wish to use performance-based methods
for these fire protection program elements and minimum design
requirements shall submit a request in the form of an application for
license amendment under Sec. 50.90. The Director of the Office of
Nuclear Reactor Regulation, or a designee of the Director, may approve
the application if the Director or designee determines that the
performance-based approach;
(A) Satisfies the performance goals, performance objectives, and
performance criteria specified in NFPA
[[Page 33551]]
805 related to nuclear safety and radiological release;
(B) Maintains safety margins; and
(C) Maintains fire protection defense-in-depth (fire prevention,
fire detection, fire suppression, mitigation, and post-fire safe
shutdown capability).
(3) Compliance with NFPA 805.
(i) A licensee may maintain a fire protection program that complies
with NFPA 805 as an alternative to complying with paragraph (b) of this
section for plants licensed to operate before January 1, 1979, or the
fire protection license conditions for plants licensed to operate after
January 1, 1979. The licensee shall submit a request to comply with
NFPA 805 in the form of an application for license amendment under
Sec. 50.90. The application must identify any orders and license
conditions that must be revised or superseded, and contain any
necessary revisions to the plant's technical specifications and the
bases thereof. The Director of the Office of Nuclear Reactor
Regulation, or a designee of the Director, may approve the application
if the Director or designee determines that the licensee has identified
orders, license conditions, and the technical specifications that must
be revised or superseded, and that any necessary revisions are
adequate. Any approval by the Director or the designee must be in the
form of a license amendment approving the use of NFPA 805 together with
any necessary revisions to the technical specifications.
(ii) The licensee shall complete its implementation of the
methodology in Chapter 2 of NFPA 805 (including all required
evaluations and analyses) and, upon completion, modify the fire
protection plan required by paragraph (a) of this section to reflect
the licensee's decision to comply with NFPA 805, before changing its
fire protection program or nuclear power plant as permitted by NFPA
805.
(4) Risk-informed or performance-based alternatives to compliance
with NFPA 805. A licensee may submit a request to use risk-informed or
performance-based alternatives to compliance with NFPA 805. The request
must be in the form of an application for license amendment under Sec.
50.90 of this chapter. The Director of the Office of Nuclear Reactor
Regulation, or designee of the Director, may approve the application if
the Director or designee determines that the proposed alternatives:
(i) Satisfy the performance goals, performance objectives, and
performance criteria specified in NFPA 805 related to nuclear safety
and radiological release;
(ii) Maintain safety margins; and
(iii) Maintain fire protection defense-in-depth (fire prevention,
fire detection, fire suppression, mitigation, and post-fire safe
shutdown capability).
* * * * *
(f) Licensees that have submitted the certifications required under
Sec. 50.82(a)(1) shall maintain a fire protection program to address
the potential for fires that could cause the release or spread of
radioactive materials (i.e., that could result in a radiological
hazard). A fire protection program that complies with NFPA 805 shall be
deemed to be acceptable for complying with the requirements of this
paragraph.
* * * * *
Dated at Rockville, Maryland, this 8th day of June, 2004.
For the Nuclear Regulatory Commission.
Annette Vietti-Cook,
Secretary of the Commission.
[FR Doc. 04-13522 Filed 6-15-04; 8:45 am]
BILLING CODE 7590-01-P